Spaced Aerial Cable SAC CABLE

  • Description
Product Detail

Overhead Cable Spaced Aerial Cable SAC Cable


Product Application
This Aluminium Insulated cable is used for the power transmission and distribution line. The SAC Cable voltage included the 0.6/1kv ,25KV and 36kv Cable. 


Product Structure
0.6/1KV Standard:IEC60502
1. Conductor : Compacted hard-drawn aluminum wires
2. Insulation : Cross-linked polyethylene (XLPE)


3. Cross-section Area Range: 10-300 mm2
25KV & 35 KV Standard: ICEA S66-524


Conductor Compact stranded hard drawn Aluminium wires
Conductor Sizes 35 mm2 up to 240 mm2


Conductor Shield :Semi conducting cross-linked polyethylene


Insulation:Track resistant cross-linked polyethylene

Technical Data


0.6/1kv Overhead cable Technical Data.

Conductor Nominal  Area (mm)

Conductor Dia. (mm)

Insulation Thickness (mm)

Approx Cable Dia.

Cable Weight (Kg/km)

Cable Breaking Load N

DC resistance at 20 ?(ohm/km)

10

3.8

1.0

5.8

45

3140

3.08

16

4.8

1.2

7.2

70

5024

1.91

25

6.0

1.2

8.4

97

7524

1.20

35

7.0

1.4

9.8

136

10354

0.868

50

8.3

1.4

11.1

176

14202

0.641

70

10

1.4

12.8

237

20708

0.443

95

11.7

1.6

14.9

331

27454

0.32

120

13.0

1.6

16.2

408

34678

0.253

150

14.6

1.8

17.7

513

42066

0.206

185

16.2

2.0

20.2

616

53466

0.164

240

18.4

2.2

22.8

798

69356

0.125

300

20.6

2.4

24.4

1016

86698

0.100

25KV SAC CABLE

No. Of the core

Nominal  Cross Sectional Area(mm2)

Min  no. Of the wire (No.)

Dia.  Of conductor approx. (mm)

Thickness  of the insulation

Thickness  of
  the  Sheath (mm)

Overall  Diameter (mm)

Max  D.c. Resistance at 20 ? (ohm/km)

Min  Breaking Load of the conductor (N)

1

35

7

6.96

3.175

3.175

20.88

0.868

5,591

50

7

8.28

3.175

3.175

22.20

0.641

7,313

70

18

9.80

3.175

3.175

23.72

0.443

10,420

95

18

11.45

3.175

3.175

25.37

0.320

14,098

120

18

12.95

3.175

3.175

26.87

0.253

18,518

150

18

14.20

3.175

3.175

28.12

0.206

22,457

185

34

15.98

3.175

3.175

29.90

0.164

28,974

240

34

18.47

3.175

3.175

32.39

0.125

37,506

35 KV SAC CABLE

No. Of the core

Nominal  Cross Sectional Area(mm2)

Min  no. Of the wire (No.)

Dia.  Of conductor approx. (mm)

Thickness  of the insulation

Thickness  of
  the  Sheath (mm)

Overall  Diameter (mm)

Max  D.c. Resistance at 20 ? (ohm/km)

Min  Breaking Load of the conductor (N)

1

35

7

6.96

4.445

3.175

23.42

0.868

5,591

50

7

8.28

4.445

3.175

23.52

0.641

7,313

70

18

9.80

4.445

3.175

26.26

0.443

10,420

95

18

11.45

4.445

3.175

27.91

0.320

14,098

120

18

12.95

4.445

3.175

29.41

0.253

18,518

150

18

14.20

4.445

3.175

30.66

0.206

22,457

185

34

15.98

4.445

3.175

32.44

0.164

28,974

240

34

18.47

4.445

3.175

34.93

0.125

37,506

Send your message to this supplier
To:  

Huatong Cable Inc

* Content:  

For better quotations, include:

- A self introduction

- Special requests, if any

Quantity:  
  
You May Like
Not exactly what you want? One request, multiple quotations Get Quotations Now >>
China Mainland Favorites
Transaction Level:

* Quantity: